MIC Chinese Simplified Chinese Traditional English

Home » Product Directory » Industrial Equipment & Components » Refrigeration & Ventilation » Air Cooled Screw Type Chillers (AGS-150ADH ~ AGS-170ADH )

Add to Basket

Air Cooled Screw Type Chillers (AGS-150ADH ~ AGS-170ADH )

Air Cooled Screw Type Chillers (AGS-150ADH ~ AGS-170ADH )
Air Cooled Screw Type Chillers (AGS-150ADH ~ AGS-170ADH )

Product Description

Cooling capacity is from 120KW to 2500KW.
Cooling capacity is adjustable for four-segment ( 100%-75%-50%-25% ), three-segment ( 100%-66%-33% ), and one-segment control system.
BITZER and HANBELL screw compressors offer reduced energy consumption, low vibration and high resistance to liquid refrigerant returns.
Refrigerants can be chosen, R-22, R-134a, R-407c, etc.
Built-in oil pressure system can ensure the best performance without oil pump.
Custom units are our specialty.

Model
Item
 
AGS-150ADH
 
AGS-170ADH
 
nominal cooling capacity
 
kcal/h
 
344000
 
399900
 
kw
 
400
 
465
 
input power
 
kw
 
134
 
146
 
max. running current
 
A
 
330
 
430
 
power supply
 
3PH~380V 50HZ
 
refrigerant
 
type
 
R22
 
refrigerating circuit
 
2
 
type of control
 
thermostatic expansion valve
 
compressor
 
type
 
semi-hermetic screw
 
quantity
 
2
 
start-up mode
 
Y-
 
capacity control
 
0-25-50-75-100
 
condenser
 
type
 
air cooled type finned copper tube
 
power (kw)
 
12
 
13.2
 
cooling air flow
(m 3 /h)
 
140000
 
164000
 
evaporator
 
type
 
shell and tube
 
quantity
 
1
 
chilled fluid flow(m 3 /h)
 
69
 
80
 
inlet and outlet pipe diameter (inch)
 
5
 
safety protection
 
compressor over temperature, over current, high and low pressure, over temperature,flow Switch, phase sequence, phase-missing, exhaust overheating, antifreezing
 
net weight
 
kg
 
4000
 
4400
 
running weight  
 
kg
 
4350
 
4800
 
Note:
        1. nominal cooling capacity is according to:
            Inlet chilled fluid temperature: 12
            Outlet chilled fluid temperature: 7
            Inlet cooling air temperature: 35
            Outlet cooling air temperature: 45
 
         2. working range:
             The temperature range of chilled fluid is from 5 to 20;
             Temperature difference between inlet and outlet chilled fluid is from 3 to 8.
             Temperature difference between inlet and outlet cooling air is from 8 to 12.
             The chiller should be used while the ambient temperature at or below 35.
 
 We reserve the right to modify the above dimensions or parameters without further notice.
 
Trademark: Anges
Model NO.: AGS-150ADH ~ AGS-170ADH
Productivity: 600pic/month
Company: Shenzhen Anges Machinery Co., Ltd.

Click here to send inquiry

Most Popular

Quick Products