MIC Chinese Simplified Chinese Traditional English

Home » Product Directory » Industrial Equipment & Components » Refrigeration & Ventilation » Industrial Air Cooled Chillers (AC-3 ~ AC-8(D))

Add to Basket

Industrial Air Cooled Chillers (AC-3 ~ AC-8(D))

Industrial Air Cooled Chillers (AC-3 ~ AC-8(D))
Industrial Air Cooled Chillers (AC-3 ~ AC-8(D))

Product Description

Cooling capacity is from 1.5 KW to 2500 KW.
COPELAND, DAIKIN, PANASONIC, SANYO compressor, SCHNEIDER electronic components, Italian water pump and stainless steel water- tank-type evaporator can be chosen.
Precisely control water temperature with variation of +/- 10C, and the temperature ranges from 50C to 500C.
Energy saving.
Custom units are our specialty.

Model
Item
 
AC-3
 
AC-5
 
AC-6
 
AC-8(D)
 
nominal cooling capacity
 
kcal/h
 
6803
 
11094
 
13091
 
17604
 
kw
 
7.91
 
12.9
 
15.22
 
20.47
 
input power
 
kw
 
3.33
 
5.8
 
6.33
 
9.25
 
power supply
 
3PH~380V 50HZ (60HZ)
 
refrigerant
 
type
 
R22
 
type of control
 
capillary
 
compressor
 
type
 
hermetic volution (piston)
 
power(kw)
 
2.8
 
4.66
 
5.2
 
3.8*2
 
condenser
 
type
 
finned copper tube + low noise outer rotor fan
 
cooling air flow(m 3 /h)
 
3000
 
5000
 
6000
 
8000
 
evaporator
 
type
 
tank with coil (shell and tube)
 
chilled fluid flow(m 3 /h)
 
1.36
 
2.22
 
2.6
 
3.52
 
volume(L)
 
50
 
70
 
70
 
120
 
inlet and outlet pipe diameter (inch)
 
1
 
1
 
1
 
1
 
pump
 
power (kw)
 
0.37
 
0.75
 
0.75
 
0.75
 
lift(m)
 
20
 
20
 
20
 
22
 
flow switch
 
closed flow3.5L/min,disconnection flow.
 
safety protection
 
compressor over temperature, over current, high and low pressure, over temperature,flow Switch, phase sequence, phase-missing, exhaust overheating, antifreezing
 
weight
 
kg
 
135
 
175
 
180
 
320
 
dimension
 
mm
 
930*520*975
 
1140*560*1040
 
1140*560*1040
 
1300*720*1350
 
Note: 1. The nominal cooling capacity is according to:
            Inlet chilled fluid temperature: 12
            Outlet chilled fluid temperature: 7
            Inlet cooling air temperature: 30
            Outlet cooling air temperature: 38
        2. Working range:
           The temperature range of chilled fluid is from 5 to 35;
           Temperature difference between inlet and outlet chilled fluid is from 3 to 8.
           The machine should be used while the ambient temperature at or below 35.
We reserve the right to modify the above dimensions or parameters without further notice.
 
Trademark: Anges
Model NO.: AC-3 ~ AC-8(D)
Productivity: 600pic/month
Company: Shenzhen Anges Machinery Co., Ltd.

Click here to send inquiry

Most Popular