MIC Chinese Simplified Chinese Traditional English

Home » Product Directory » Industrial Equipment & Components » Refrigeration & Ventilation » Screw Type Chillers ( AGS-040ASH ~ AGS-060ASH )

Add to Basket

Screw Type Chillers ( AGS-040ASH ~ AGS-060ASH )

Screw Type Chillers ( AGS-040ASH ~ AGS-060ASH )
Screw Type Chillers ( AGS-040ASH ~ AGS-060ASH )

Product Description

Screw type chiller are offered of a veriety of applications and industries:
1. Plastic & Rubber (injection molding, extrusion, blow molding, bottling, plastic film)
2. Chemical & Pharmacy (laboratories)
3. Industrial cleaning (ultrasonic cleaning)
4. Printers
5. Textiles, etc.

                                     Model
Item 
AGS-040ASH
 
AGS-050ASH
 
AGS-060ASH
 
nominal cooling capacity
 
kcal/h
 
86000
 
111800
 
129000
 
kw
 
100
 
130
 
150
 
input power
 
kw
 
39
 
43
 
49
 
max. running current
 
A
 
91
 
116
 
122
 
power supply
 
3PH~380V 50HZ
 
refrigerant
 
type
 
R22
 
refrigerating circuit
 
1
 
type of control
 
thermostatic expansion valve
 
compressor
 
type
 
semi-hermetic screw
 
quantity
 
1
 
start-up mode
 
Y- Delta
 
capacity control
 
0-25-50-75-100
 
condenser
 
type
 
air cooled type finned copper tube
 
power ( kw )
 
3.9
 
4.3
 
5.5
 
cooling air flow
(m 3 /h)
 
40000
 
48000
 
60000
 
evaporator
 
type
 
shell and tube
 
quantity
 
1
 
chilled fluid flow(m 3 /h)
 
17
 
22
 
26
 
inlet and outlet pipe diameter (inch)
 
3
 
safety protection
 
compressor over temperature, over current, high and low pressure, over temperature,flow Switch, phase sequence, phase-missing, exhaust overheating, antifreezing
 
net weight
 
kg
 
1600
 
1800
 
1950
 
running weight  
 
kg
 
1800
 
2000
 
2150
 
Note: 1. nominal cooling capacity is according to:
        Inlet chilled fluid temperature: 12 Deg. C
        Outlet chilled fluid temperature: 7 Deg. C
        Inlet cooling air temperature: 35 Deg. C 
        Outlet cooling air temperature: 45 Deg. C 
     2. working range:
        The temperature range of chilled fluid is from 5 Deg. C to 20 Deg. C;
        Temperature difference between inlet and outlet chilled fluid is from 3 Deg. C to 8 Deg. C.
        Temperature difference between inlet and outlet cooling air is from 8 Deg. C to 12 Deg. C.
        The machine should be used while the ambient temperature at or below 35 Deg. C.
We reserve the right to modify the above dimensions or parameters without further notice.
 