Air Cooled Screw Type Chillers (AGS-180ASH ~ AGS-220ASH)
![]() Air Cooled Screw Type Chillers (AGS-180ASH ~ AGS-220ASH) |
Product Description
Cooling capacity is from 120KW to 2500KW.
Cooling capacity is adjustable for four-segment ( 100%-75%-50%-25% ), three-segment ( 100%-66%-33% ), and one-segment control system.
BITZER and HANBELL screw compressors offer reduced energy consumption, low vibration and high resistance to liquid refrigerant returns.
Refrigerants can be chosen, R-22, R-134a, R-407c, etc.
Built-in oil pressure system can ensure the best performance without oil pump.
Custom units are our specialty.
| Model Item | AGS-180ASH | AGS-200ASH | AGS-220ASH | ||||
| nominal cooling capacity | kcal/h | 430000 | 490200 | 533200 | |||
| kw | 500 | 570 | 620 | ||||
| input power | kw | 158 | 183 | 201 | |||
| max. running current | A | 395 | 454 | 493 | |||
| power supply | 3PH~380V 50HZ | ||||||
| refrigerant | type | R22 | |||||
| refrigerating circuit | 1 | ||||||
| type of control | thermostatic expansion valve | ||||||
| compressor | type | semi-hermetic screw | |||||
| quantity | 1 | ||||||
| start-up mode | Y- | ||||||
| capacity control | 0-25-50-75-100 | ||||||
| condenser | type | air cooled type finned copper tube | |||||
| power (kw) | 15 | 18 | 21 | ||||
| cooling air flow (m 3 /h) | 180000 | 210000 | 235000 | ||||
| evaporator | type | shell and tube | |||||
| quantity | 1 | ||||||
| chilled fluid flow(m 3 /h) | 86 | 98 | 107 | ||||
| inlet and outlet pipe diameter (inch) | 6 | ||||||
| safety protection | compressor over temperature, over current, high and low pressure, over temperature,flow Switch, phase sequence, phase-missing, exhaust overheating, antifreezing | ||||||
| net weight | kg | 4500 | 4800 | 5300 | |||
| running weight | kg | 4900 | 5300 | 5800 | |||
| Note: 1. nominal cooling capacity is according to: Inlet chilled fluid temperature: 12 Outlet chilled fluid temperature: 7 Inlet cooling air temperature: 35 Outlet cooling air temperature: 45 2. working range: The temperature range of chilled fluid is from 5 to 20; Temperature difference between inlet and outlet chilled fluid is from 3 to 8. Temperature difference between inlet and outlet cooling air is from 8 to 12. The chiller should be used while the ambient temperature at or below 35. We reserve the right to modify the above dimensions or parameters without further notice. | |||||||
| Trademark: | Anges |
| Model NO.: | AGS-180ASH ~ AGS-220ASH |
| Productivity: | 600pic/month |
| Company: | Shenzhen Anges Machinery Co., Ltd. |
Most Popular
-

Adhesive Tape (AF2525,AF3025,AF4025) Features: 1)A high tensile strength aluminum ... -

Acoustic Insulated Flexible Duct Acoustic Insulated Flexible Duct Features: ... -

Ventilation Fan (LE-8) BEST ventilation fan choose special steel ...
-

Night Curtain Polycore Technology night blind systems make a ... -

Chiller (LS SERIES) 1. Product description The LS series Products ... -

Fume Hood (112) Type of Hood: Bench Hood Overall dimensions: ...
-

Oven fan motor(YJ61) Motor size: 1. Stator diameter: 61.5mm 2. ... -

Counterflow Cooling Tower SALIENT FEATURES CASING: The casing is made out ... -

Water Source Heat Pump Packaged Hang Cabinet ... Water source heat pump unit is a kind of new ...
-

Tube Ice Machine ICESTA tube ice--- Mainly used for human ... -

Plate Ice Machine Focusun Plate Ice Machine is produced by being ... -

Air Filter & Ventilation Filter Air Filter & Ventilation Filter description: ...
-

Outdoor Gas Barbecue Our main products in production include: Barbecue ... -

Flake Ice Machine (LT-20000) The range of ice making capacity is from ... -

Manifold/Manifold Valve/Manifold Gauges Kit (SH-M30336A) Suited for R134A Aluminium body with dual o-ring ...
Quick Products |
Inquiry Basket (