Product Description

AC/W industrial water chillers are widely used in industries including the plastics, electronic manufacturing, electroplating, pharmacy, chemical engineering, ultrasonic cooling, and printing.

COPELAND, DAIKIN, PANASONIC, SANYO compressor, SCHNEIDER electronic components, Italian water pump and stainless steel water- tank-type evaporator can be chosen.
Precisely control water temperature with variation of +/- 1ºC, and the temperature ranges from 5ºC to 50ºC.
Energy saving.
Customized units are our specialty..

                                              Model
Item
 
AC-3
 
nominal cooling capacity
 
kcal/h
 
6803
 
kw
 
7.91
 
input power
 
kw
 
3.33
 
power supply
 
3PH~380V/50HZ
 
refrigerant
 
type
 
R22
 
type of control
 
capillary
 
compressor
 
type
 
hermetic scroll(piston)
 
power(kw)
 
2.8
 
condenser
 
type
 
finned copper tube + low noise outer rotor fan
 
cooling air flow (m 3 /h)
 
3000
 
evaporator
 
type
 
tank with coil ( shell and tube )
 
chilled fluid flow (m 3 /h)
 
1.36
 
volume (L)
 
50
 
inlet and outlet pipe diameter (inch)
 
1
 
water pump
 
power (kw)
 
0.37
 
lift (m)
 
20
 
safety protection
 
compressor over temperature, over current, high and low pressure, over temperature,flow switch, phase sequence, phase-missing, exhaust overheating, antifreezing
 
weight
 
kg
 
135
 
dimension
 
mm
 
930*520*975
 
Note: 1. Nominal cooling capacity is according to:
             Inlet chilled fluid temperature: 12 centigrade degree 
             Outlet chilled fluid temperature: 7 centigrade degree 
             Inlet cooling air temperature: 30 centigrade degree 
             Outlet cooling air temperature: 38 centigrade degree 

          2. Working range:
             The temperature range of chilled fluid is from 5 centigrade degree to 35 centigrade degree;
              Temperature difference between inlet and outlet chilled fluid is from 3 centigrade degree to 8 centigrade degree.
             It is better to use the chiller while the ambient temperature at or below 35 centigrade degree.